Acu – what is the overview Air Clean Unit

acu-ZN-A4105D

Many different terms in clean room that you should and need to learn, but not what device also has multiple materials for your reference. Air Clean Unit, or what is Acu, what is the activity and the characteristics of the ACU how. Today we will introduce for you about the term Air Clean Unit clean room, and a number of specifications and equipment Acu today’s latest

Concept Air Clean Unit is what – Acu is what?

acu-la-gi

Concept Air Clean Unit is a device for the app to handle the air has a conditioning effect and the ability to clean the air. 

ACU is much customers appreciate by design, compact size, stable operation and energy saving. The device ACU professional is used for system clean room manufacturing, pharmaceutical, cosmetic, medicine, areas electronic manufacturing, scientific research,…

Air Clean Unit clean room can be guaranteed to be level, clean class 1000 that absolutely do not need to use the next to lift the grid. The device ACU allows the system to operate in a stable manner by creating the flow in the layer in the vertical direction by the duct system placed above the ceiling.

Also like AHU, then the ACU is the processor air, however, it does not need separate temperature controller, humidity right on the machine as AHU. That ACU integrated always temperature controller, humidity inside the machine. It is by this point that it will be more convenient in the stitch used operating, saves area better.

Characteristics of the device ACU clean room:

1. ACU can be used for any type of clean room in any technical terms or different scale.

2. Air Clean Unit is very easy in installation and repair. Also very easy for maintenance activities because of simple structure, machine, and compact size. When the selected ACU, then you can be assured of texture and expense, because it does not require too much handling equipment other air again in the clean room.

3. Operating noise level less than 65dB, so when running work very quiet no noise affects the working process inside the clean room.

4. After the installation of the ACU done completely can move the location of the machine from this room to the other and then back installation. In addition, you can adjust the level of cleaning required use.

5. Control the temperature and humidity of room, easy clean, the frequency of small circulation.

6. Save the investment cost and operating activities in case there are multiple areas clean room need processed individually to separate.

Specifications of the device ACU clean room categories new today:

today on the market there are many products sample ACU room clean so different specifications, characteristics, dimensions also varied.

Today MIGCO will introduce for you about the ACU ZN with slim design, lightweight, flexible, clean air fast. Line ZN have 3 size vary in accordance with the various needs of customers: ZN-A2502D, ZN-A4105D and ZN-A6112 ( including ZN-A6112 and ZN-A6112P)

  • size air outlet in turn is ZN-A2502D ( 225 × 205 mm),  ZN-A4105D( 360 × 360 mm),  ZN-A6112 and ZN-A6112P equal 578 × 568 mm.
  • The rate of removal of main filter: HEPA filter with 99.99% of particles 0.3 µm and above
  • voltage supply 24VDC ± 10%, Ripple (p-p): maximum 10% 
  • Amount of wind: 5 levels. Can install by button operation. Can set according to serial (RS-422 or RS-485 * 1) communication
  • noise when running Flow-level wind 3: 53 dB 
  • Fan motor Compact DC brushless
  • fan motor ACU:blowers centrifugal brushless DC compact x 2. Turbo fan brushless DC x 1 D 
  • The indicator on the device: active status: Green / Red. Adjustment button air: blue 
  • external output ACU: 30 VDC, max 50 mA. Voltage balance: maximum of 1 V. with a load current of 10 mA, maximum of 2 V. with the load line is 50 mA. 

With ZN-A2502D and ZN-A4105D

acu-ZN-A4105D

Alarm output 1: common alarm output 1 is ON. Alarm output 1 will turn OFF when one of the following problems occur:  (Please check indicator to find out the problems do happen.)

  • Filter clogged.
  • Fan faulty
  • Alarm clean metal discharge (when ZN-J-series Ionizer (sold separately) is connected)
  • Error discharge (when ZN-J-series Ionizer (sold separately) is connected)

alarm output 2: common alarm output 2 is ON. Only be turned on when the ZN-J-series Ionizer is connected.

  • Output alarm 2 OFF to indicate that the cleaning ZN-J-series Ionizer is necessary.

With 2 product lines ZN-A6112:

Alarm output operation of the fan:the usual will Turn ON. And only turn off when the fan is not spinning (even if the power source is OFF or in standby mode), there is a problem or filter clogged (only happens with ZN-A6112P) 

  • temperature Range ambient: operating and storage: 0 to 40 ° C (no freezing or condensation) 
  • humidity Range ambient operating and storage: 35% to 85% (no condensation) 
  • Apply pollution degree : pollution degree 2 

On this is 1 of detailed information about ACU’s what characteristics as well as parameters 1 few lines stand out. You want advice or have more information about ACU or air-conditioning system, clean room, please contact MIGCO.

Read more:

> hvac System is what the principle and structure, hvac system

> Ahu what is? Structure and principle of operation system Ahu

> distinguish Ahu and chiller

Về chúng tôi

Công ty TNHH MIG là đại diện cho các thương hiệu khí hàng đầu thế giới như: Soxal – Airliquide, Cryolor, Praxair, Nox… tại VN chuyên phân phối các loại khí công nghiệp, khí y tế, khí đặc biệt nhiều thành phần cùng nhiều thiết bị ngành khí như bơm lỏng, vỏ chai, van, bộ hóa hơi, bồn lỏng…
Trụ Sở: Số 8 đường số 15, Kp3, Phường An Khánh, THành Phố Thủ Đức, Tp. Hồ Chí Minh
MST : 0310873910

Thông Tin Liên Hệ

Văn phòng đại diện: Số 8 đường số 15, Kp3, Phường An Khánh, THành Phố Thủ Đức, Tp. Hồ Chí Minh
Tel: 0283 620 9629
Hotline: 0918 37 77 66 - 093 77 55 800
Email: Tranhuuvinh@migco.vn
Cart
  • Your cart is empty Browse Shop